Power Loss in Top Runner Transformers of 500 kVA or Less
Author: kegasaExecutions: 13
※ This library was created by a member. This site is not responsible for its content.
Losses in Top Runner transformers rated at 500 kVA or less. Comparison of the 2006, 2014, and 2026 standards. Frequencies: 50 Hz and 60 Hz
L3P50Hz2006 = 23.8*(kVA)^(0.653);
L3P50Hz2014 = 16.6*(kVA)^(0.696);
L3P50Hz2026 = 14.5*(kVA)^(0.694);
L3P60Hz2006 = 22.6*(kVA)^(0.651);
L3P60Hz2014 = 17.3*(kVA)^(0.678);
L3P60Hz2026 = 14.4*(kVA)^(0.681);
L1P50Hz2006 = 15.3*(kVA)^(0.696);
L1P50Hz2014 = 11.2*(kVA)^(0.732);
L1P50Hz2026 = 9.34*(kVA)^(0.737);
L1P60Hz2006 = 14.4*(kVA)^(0.698);
L1P60Hz2014 = 11.1*(kVA)^(0.725);
L1P60Hz2026 = 8.6*(kVA)^(0.744);
L3P50Hz2014 = 16.6*(kVA)^(0.696);
L3P50Hz2026 = 14.5*(kVA)^(0.694);
L3P60Hz2006 = 22.6*(kVA)^(0.651);
L3P60Hz2014 = 17.3*(kVA)^(0.678);
L3P60Hz2026 = 14.4*(kVA)^(0.681);
L1P50Hz2006 = 15.3*(kVA)^(0.696);
L1P50Hz2014 = 11.2*(kVA)^(0.732);
L1P50Hz2026 = 9.34*(kVA)^(0.737);
L1P60Hz2006 = 14.4*(kVA)^(0.698);
L1P60Hz2014 = 11.1*(kVA)^(0.725);
L1P60Hz2026 = 8.6*(kVA)^(0.744);
| Three-phase, 50 Hz, 2006 | W |
| Three-phase, 50 Hz, 2014 | W |
| Three-phase, 50 Hz, 2026 | W |
| Three-phase, 60 Hz, 2006 | W |
| Three-phase, 60 Hz, 2014 | W |
| Three-phase, 60 Hz, 2026 | W |
| Single-phase, 50 Hz, 2006 | W |
| Single-phase, 50 Hz, 2014 | W |
| Single-phase, 50 Hz, 2026 | W |
| Single-phase, 60 Hz, 2006 | W |
| Single-phase, 60 Hz, 2014 | W |
| Single-phase, 60 Hz, 2026 | W |