Power Loss in Top Runner Transformers of 500 kVA or Less

Author: kegasaExecutions: 13

※ This library was created by a member. This site is not responsible for its content.

Manage Bookmarks
Losses in Top Runner transformers rated at 500 kVA or less. Comparison of the 2006, 2014, and 2026 standards. Frequencies: 50 Hz and 60 Hz
L3P50Hz2006 = 23.8*(kVA)^(0.653);
L3P50Hz2014 = 16.6*(kVA)^(0.696);
L3P50Hz2026 = 14.5*(kVA)^(0.694);
L3P60Hz2006 = 22.6*(kVA)^(0.651);
L3P60Hz2014 = 17.3*(kVA)^(0.678);
L3P60Hz2026 = 14.4*(kVA)^(0.681);
L1P50Hz2006 = 15.3*(kVA)^(0.696);
L1P50Hz2014 = 11.2*(kVA)^(0.732);
L1P50Hz2026 = 9.34*(kVA)^(0.737);
L1P60Hz2006 = 14.4*(kVA)^(0.698);
L1P60Hz2014 = 11.1*(kVA)^(0.725);
L1P60Hz2026 = 8.6*(kVA)^(0.744);
Electrical Capacity (kVA)
kVA
Three-phase, 50 Hz, 2006 W
Three-phase, 50 Hz, 2014 W
Three-phase, 50 Hz, 2026 W
Three-phase, 60 Hz, 2006 W
Three-phase, 60 Hz, 2014 W
Three-phase, 60 Hz, 2026 W
Single-phase, 50 Hz, 2006 W
Single-phase, 50 Hz, 2014 W
Single-phase, 50 Hz, 2026 W
Single-phase, 60 Hz, 2006 W
Single-phase, 60 Hz, 2014 W
Single-phase, 60 Hz, 2026 W

No customer feedback for this calculation yet.